Tankless Water Heater Calculator: Flow, Rise and BTU

Work out the heat a tankless water heater must add from your hot water flow and temperature rise, why winter matters, and how to read a maker's flow chart.

Key takeaways

  • Heat output = 500 × gallons per minute × temperature rise.
  • Colder inlet water means a bigger rise, so a unit makes less flow in winter.
  • A model's rating chart, not this formula, says what it will deliver.

Enter the hot water flow you want at the same time, and how many degrees the water needs to rise. The result is the heat output needed. It isn't a promise that any model will deliver it.

  • Heat output needed192,500 BTU/hr500 × flow × temperature rise
  • Electric equivalentAbout 56.4 kWA large electric load; ask an electrician about your service

Nothing you enter leaves your browser. Output needed at the unit. Actual flow depends on the model, inlet water and installation, so check its rating chart.

Show the math with your numbers
  1. Heat: 500 × 5.5 gpm × 70°F = 192,500 BTU/hr
  2. Electric: 192,500 ÷ 3,412 = 56.4 kW
What if: temperature rise
Temperature riseHeat output needed
40°F110,000 BTU/hr
50°F137,500 BTU/hr
60°F165,000 BTU/hr
70°F (yours)192,500 BTU/hr
80°F220,000 BTU/hr

How the calculator works

BTU per hour = 500 × gallons per minute × temperature rise in °F

The 500 comes from about 8.33 pounds per gallon × 60 minutes per hour. To convert to electric power, divide by 3,412 for kilowatts. Temperature rise is your hot water setting minus your incoming water temperature.

This is standard water heating math, which we read on trade and retail pages rather than a government source.

Worked example

5.5 gallons per minute with a 70°F rise:

  • 500 × 5.5 × 70 = 192,500 BTU per hour
  • 192,500 ÷ 3,412 = about 56 kW if electric

That second number shows why electric whole-house units can run into a home's service limits. Ask an electrician before you plan on one.

Why winter matters

Flow and rise trade off. With the same output, a bigger rise means less flow. Using a unit able to add 150,000 BTU per hour, for example:

Rise Flow it could support
40°F 7.5 gpm
60°F 5.0 gpm
80°F 3.75 gpm

So size for your coldest inlet temperature, and ask a local plumber what that is.

Not all flow is hot water

A shower mixes hot and cold, so it draws less than its full flow from the heater:

Hot share = (mixed temperature − cold) ÷ (hot − cold)

A 2.0 gpm shower at 105°F, with 120°F hot and 50°F inlet water, draws about 1.57 gpm of hot water, according to our math. Add up what you'd run at once using the hot share. We don't publish default fixture flows, as we haven't sourced them, so check your own fixtures.

Compare with a real model

  1. Work out your flow and coldest-weather rise.
  2. Find the model's published flow-at-rise chart.
  3. Check gas line, venting and electrical requirements with a licensed professional. Replacing a tank with a tankless unit can change all three, and may need a permit.

For a storage tank instead, use the first-hour rating worksheet.

Frequently asked questions

How big a tankless water heater do I need?

Work out the flow you'd use at once and your coldest temperature rise, then compare with the model's own chart.

How many showers can one run?

It depends on the unit, your shower flow and your inlet temperature. Use the math above with your own numbers.

Is the BTU rating the same as output?

Not always. Rated input and delivered heat can differ, so use the maker's flow chart for the final check.